6.2.1 |
Neither supply nor exhaust air ducts from engine spaces or engine exhaust outlets shall open into an
accommodation space. |
6.2.2 |
Electrical components installed in gasoline engine spaces, gasoline tank spaces, and any connecting
spaces not open to the atmosphere shall be ignition protected in accordance with Section 8 of this
Standard. |
6.3 |
Gasoline Engine and Fuel Tank Space Ventilation ^ |
6.3.1 |
Application ^ |
6.3.1.1 |
This subsection applies to all vessels, regardless of length or accommodation that have gasoline
engines for propulsion or other purposes. |
6.3.2 |
Removal of Combustible Vapours ^ |
6.3.2.1 |
Combustible vapours shall be removed from closed engine and fuel tank spaces by means of a
ventilation system. |
6.3.2.2 |
Open engine or fuel tank spaces do not require a separate ventilation system if in compliance with
subsection 6.3.3. |
6.3.3 |
Open Spaces Vessel Construction ^ |
6.3.3.1 |
A separate ventilation system is not required if an engine or fuel tank space has the following (see
Figure 6–1):
(a) at least 0.34 m2 (3.5 ft2) of area exposed to the atmosphere per cubic metre (35 ft3) of net space
volume; and
(b) no long or narrow unvented spaces in which a flame front might propagate. |
6.3.3.2 |
The net space volume is the volume of the engine or fuel tank space plus the volume of connecting
spaces, unless the connecting spaces either:
(a) connect to spaces already ventilated by ducting; or
(b) themselves qualify as open spaces. |
6.3.3.3 |
Spaces connecting with spaces open to the atmosphere, which have interconnecting openings with
an area equal to 2% or less of the separation bulkhead, shall not be considered as open spaces. |
6.3.3.4 |
The volumes of adjacent spaces shall be included in the calculation of duct sizes if the collective area
of the openings in the separation bulkheads exceeds 2% of the separation bulkhead area between
these spaces. |
6.3.3.5 |
The separation bulkhead area used for the calculations in paragraph 6.3.3.4 and 6.3.3.3 shall be
calculated using a height that is the lesser of either the distance between the bottom and top of the
bulkhead between the spaces, or 750 mm (30 in). |
6.3.3.6 |
Long narrow spaces formed by side panels or accommodation decks shall have openings at both ends
or along the sides in order to qualify as open spaces. |
6.3.5 |
Underway Ventilation ^ |
6.3.5.1 |
Every closed engine space and every closed space containing a permanent or portable fuel tank shall
be provided with a ventilation system designed to remove any accumulation of combustible vapours. |
6.3.5.2 |
At least one exhaust duct shall extend down to the bilge of the space from which the fumes are to be
expelled. If the space is an engine space, the exhaust duct entrances shall be located as nearly as
practicable under the engine, or engines. |
6.3.5.3 |
Duct termination in bilges shall be secured above the level of normal accumulations of
bilge water. |
6.3.5.4 |
Ventilation openings shall be located, where practicable, on the deck, but so located to minimize the
ingress of water, taking into account all service conditions of heel, trim, wave action, loading, and
reverse operations. |
6.3.5 |
Ducts ^ |
6.3.6.1 |
The minimum collective internal cross-sectional area of ducts shall be calculated as per ABYC
Standards for Small Craft H–2. |
6.3.6.2 |
If the engine or fuel tank space connects to an adjoining closed space, the total net volume of both
the space and closed space shall be used to determine the required duct size. |
6.3.6.3 |
Non-metallic materials used for ventilating ducts and components installed below deck shall be
capable of continuous exposure to a temperature range of –30°C to 85°C without failure. |
6.3.6.4 |
Non-metallic ventilating ducts and components shall be installed at least 230 mm (9 in) clear to the
side and below, and 460 mm (18 in) above any surface capable of reaching a temperature of 150°C,
unless those components are designed for use in higher temperature locations. |
6.3.7 |
Cowls and Ventilation Openings ^ |
6.3.7.1 |
External openings of intakes and exhausts shall be located and oriented to prevent entry of fuel vapors.
In no instance shall the intakes and exhausts be closer than 15 inches (380mm) from the gasoline fill
and tank vent fittings. |
6.3.7.2 |
No component of the ventilation system shall restrict the minimum required duct size. |
6.3.7.3 |
Cowl ventilators shall be rated and labeled with the maximum effective cross-sectional area. |
6.3.7.4 |
The cowl ventilator shall be installed over the duct to maintain the rated area in accordance with the
cowl manufacturer’s specifications. |
6.3.7.5 |
Reduced airflow due to reduced area from screens shall be accounted for by using oversized cowls or
ventilation openings. |
6.3.7.6 |
If louvers are used as cowl ventilators, they shall create an airflow equivalent to that produced by the
required minimum cowl ventilator size. |
6.3.8 |
Blowers ^ |
6.3.8.1 |
The underway ventilation system shall be supplemented by a mechanical blower in order to remove
combustible vapours from engine spaces prior to starting the engine. |
6.3.8.2 |
Blowers may be installed with separate ducting or installed in the underway exhaust duct as illustrated
in Figure 6–2. |
6.3.8.3 |
Blowers shall be mounted as high as practicable above the bilge low point to prevent contact with
bilge fluid, except for blowers designed in combination with bilge pumps, which can be operated
submerged. |
6.3.8.4 |
Blower outlet fittings shall not have less effective area than blower intakes. |
6.3.8.5 |
Blowers shall not be wired in the ignition circuit to run continuously, unless rated by the manufacturer
for continuous operation. |
6.3.8.6 |
Blower motors shall be of a sealed type or ignition protected and shall be suitable for marine
atmosphere. |
6.3.8.7 |
A blower instruction placard shall be provided at every engine ignition switch indicating the length
of blower operating time that is required to clear the engine space prior to starting the engine. |
6.3.8.8 |
The blower shall be designed for a minimum of four minutes continuous operation, more if required,
to clear any space of vapours. |
6.3.8.9 |
Table 6–1 provides the formulae for sizing of blowers in order to achieve complete evacuation in four
(4) minutes. |