PREVIOUS | NEXT
CONSTRUCTION OF A NEW FISHING VESSEL
If the proposed vessel is going to be larger than 15 tons, gross tonnage, the sections
of the Regulations dealing with construction will apply and the following procedure should
be followed:
Before starting construction, the owner should send to the nearest Ship Safety office
as much of the information listed in Schedule I of the Regulations as possible, including
data on the vessel's electrical systems. The Inspector will then reply stating whether or
not the proposals are acceptable. The Inspectors may also request alterations sufficient
to ensure that the vessel will meet the average standards of construction that have, in
the past, been found satisfactory in that district, and that it will comply with the
construction rules laid out in the Regulations.
The owner must also notify the Inspector when commencing construction
and at the various stages of construction mentioned in section 44 of the Regulations. The
Inspector will visit the boat during construction and, on these occasions, explain the
requirements of the Regulations, if necessary. At these times, the Inspector will also
acquire any of the information that the owner was unable to submit on the first contact
with the Ship Safety office.
![FIGURE 1 - TYPICAL DIESEL FUEL SYSTEM - Image](/web/20060212065139im_/https://www.tc.gc.ca/MarineSafety/TP/Tp782/images/Image72.gif)
FIGURE 1 - TYPICAL DIESEL FUEL SYSTEM ^
![FIGURE 2 - TYPICAL GASOLINE FUEL SYSTEM - Image](/web/20060212065139im_/https://www.tc.gc.ca/MarineSafety/TP/Tp782/images/Image73.gif)
FIGURE 2 - TYPICAL GASOLINE FUEL SYSTEM ^
Figures 1 and 2 show, in a diagrammatic way, typical fuel tank installations, which
comply with the Regulations. The Regulations concerning fuel tanks also state that there
must be a means of stopping the engine, outside the engine space, in addition to the
shut-off valve on the fuel tank.
After the vessel is completed and all equipment placed on board, a dock and sea trial
will be held at which the Inspector will be present. This will be the final test of the
seaworthiness of the vessel. If everything is satisfactory, the Inspector will issue a
certificate of inspection that will be valid for four years.
Figure 3 shows, in diagrammatic form, a bilge-pumping arrangement that complies with
the minimum requirements of the Small Fishing Vessel Inspection Regulations, where a
single pump is used for bilge-pumping and fire-extinguishing purposes.
![FIGURE 3 - TYPICAL BILGE SYSTEM - Image](/web/20060212065139im_/https://www.tc.gc.ca/MarineSafety/TP/Tp782/images/Image75.gif)
FIGURE 3 - TYPICAL BILGE SYSTEM ^
Note If all the bilge branch line stop valves are of the screwdown non-return type,
then the non-return or swing check valve marked X need not be fitted.
ELECTRICAL INSTALLATION ^
Figure 4 and associated notes describes a typical small fishing vessel electrical
installation.
![FIGURE 4 - TYPICAL ELECTRICAL SYSTEM - Image](/web/20060212065139im_/https://www.tc.gc.ca/MarineSafety/TP/Tp782/images/Image76.gif)
FIGURE 4 - TYPICAL ELECTRICAL SYSTEM ^
SMALL VESSEL ELECTRICAL DRAWING ^
NOTES
The Basic Information Required on Electrical Drawings is as follows:
1 Batteries; type. size, capacity, voltage and location plus method of connection and
support. Battery boxes are to be lined with an antacid protection, protectively covered,
and well ventilated.
2. Generators; normally provided by the engine suppliers, should indicate K.W. Rating,
voltage and maximum current output.
3. The generator and battery should be protected by means of a double pole fused switch
or circuit breaker.
4. Generators rated less than 25 KW, and not arranged to operate in parallel, may be
protected by a multi-pole linked switch with a fuse in each insulated pole.
5. Generators arranged to operate in parallel, or any generator rated in excess of 25
KW should be protected by a circuit breaker which will open simultaneously all insulated
poles and which is provided with adjustable over current release capable of being set to
open the circuit breaker at 150 % of the continuous full load current of the generator.
6. Since most small vessels are too small for a switchboard, a suitable distribution
box, capable of carrying all the required power to the various systems, should be
substituted. This box should be capable of protecting the generator, the battery and all
outgoing circuits from short circuit faults.
7. All light fittings and power receptacles exposed to the weather, spray, or drip,
should be of marine type and water tight. Particular attention being given to upper deck
fittings and navigation lights.
8. All cables should be of the correct ampacity, having due regard to size with respect
to voltage drop, and are to be of marine approved type.
9. Method of cable support should include non-ferrous metallic clips or straps at least
every 24 inches.
10. Navigation lights should be individually switched and fused from a separate
distribution panel reserved for this purpose only, and connected directly to the main
switchboard.
11. Main engine wiring such as engine starting, voltage regulators, control and alarm
systems are normally supplied with the main engine and consequently, a sketch should be
obtained from a supplier for inclusion in the electrical drawing.
12. Provision should be made for such equipment as Echo Sounders, Radars, Radio
Telephones, 110 V.A.C. battery charging systems, where applicable, and an allowance made
for spare circuits. Equipment of different voltages are not permitted to be connected in
the same box.
13. Where voltages over 55 V are used on wood or composite hulled ships, a continuous
ground conductor should be installed to facilitate the grounding on non-conducting exposed
metal parts. The ground conductor should terminate at a copper plate not less than 2 sq.
ft. in area fitted outside the hull below the light water line so as to be fully immersed
under all conditions of heel.
14. Lightning conductors should be fitted to each mast of all wood and composite ships
and run to its own grounding plate, separate from but the same as that described in 13
above.
15. Lightning rods, conductors and grounding plate should also be included but not form
part of the ship's power supply system.
16. Notes on the drawing should provide information that would clarify the type of
equipment or material or installation advice.
GENERAL NOTES: ^
17. Cable runs to Navigation Lights are to terminate with watertight receptacles (type
KONDU V-6111 or equivalent). Navigation lights are to be wired internally with 2 conductor
rubber sheathed cable to a watertight plug (type KONDU V-6115 or equivalent).
18. All convenience outlets are to be "U" ground type.
19. Battery banks are to be protectively covered with ventilation openings fitted with
steel-gauze covering.
20. Cables will be secured with a non-ferrous metal clip no less than 610 mm apart.
21. All cables will be marine approved impervious sheathed X link insulation.
22. All instruments will be 250° scale, red lined at maximum normal operation
condition.
23. Lightning conductor shall be composed of continuous tape or wire having a section
of not less than 0.15 sq. ins. attached by copper clamps or rivets to a copper spike not
less than 0.5 inches in diameter, projecting at least 6 inches above the top of the mast.
It should terminate at a copper plate, separate from, and in addition to, the copper plate
for the grounding conductor; of area not less than two square feet, fixed outside the hull
so as to be fully immersed under all conditions of heel.
PREVIOUS | NEXT
|