Quality Control Requirement |
Acceptable |
1 |
Civil Site plan in metres (1 drawing unit = 1 m); Building/Structure plans and details in millimetres (1 drawing unit = 1 mm). |
|
2 |
Layout of Dimensioning follows CSA Standards. |
|
3 |
Line work is drafted at varied line thicknesses to clarify and distinguish graphics. |
|
4 |
Use of Major Headings (Indicator Bubbles) and scales for each drawing portion - verify indicator bubbles. |
|
5 |
North Arrow on plan view (upper right preference); Key map in title sheet to locate work. |
|
6 |
Proper Structural Grid notation; letters on horizontal, numbers on vertical, no “0” “O” or “I”. |
|
7 |
Establish clearly marked Benchmark/Control Point with description and elevation on plans/site plans. Real World Grid Coordinates System used on plans/site plans. Reference Coordinates System noted on plans with conversion factor wherever applicable. - FOR CIVIL PROJECTS ONLY. |
|
8 |
Express slope using correct numerical ratio; arrows point up slopes except drains. |
|
9 |
Titleblock information/Drawing Notes are correctly entered on drawings (i.e. As Built, Project Number). |
|
10 |
Legend and Schedules used to facilitate understanding of symbology and items lists. |
|
11 |
Proper use of text heights (2.0 mm minimum). |
|
12 |
CAD Drawing is modelled at full scale; Annotation, Dimensioning and Hatching scaled accordingly to match final viewport or block insertion scaling. |
|
13 |
PWGSC Title sheet inserted at (0, 0, 0) with scale factor of 1 and plotted at scale of 1:1 in paperspace. DO NOT EXPLODE BLOCK. |
|
14 |
No External Referencing allowed; External Referenced drawing files must be bound as block - for final Tender and As-Built drawings. |
|
15 |
Drawing must be fully purged; no extraneous drawing entities “out in space” (Unused layers, Unused blocks, Extra Layouts, etc.). Any items that cannot be purged should be noted in “README” Layer. |
|
16 |
>95% linework that should be ortho and joined must have no dangles or overlaps. |
|
17 |
Drawing file names follow correct naming scheme, i.e. project no.-sheet no. |
|
18 |
One drawing per CADD file with no unnecessary frozen or off layers. |
|
19 |
Use of PWGSC Standards Pen Configuration. |
|
20 |
>95% of drawing entities must have colour and line type “Bylayer”. |
|
21 |
Use of PWGSC Layering Standards. |
|
22 |
Only the AutoCAD Standards Fonts are used in the drawing. Non-Standards Fonts used in Consultant’s Logo to be noted in “README” Layer. |
|
23 |
Linetype scaling set up correctly i.e. ltscale/psltscale/measurement variables. |
|